Set EHBL2P to Y to enable second harmonic blocking. Use the NOT HBL2T relay word bit in the 67P1TC torque equation to prevent the instantaneous high set phase overcurrent element from operating during inrush. Among these, the second (100/120Hz) and fifth (250/300Hz) harmonics are particularly problematic, necessitating their blockage in protection relays to ensure system reliability. In this extensive guide, we explore harmonic detection and mitigation strategies, delve into their technical. Harmonic restraining in differential protection is a technique used in transformer protection to prevent false tripping during inrush or over-fluxing conditions by detecting and blocking specific harmonic currents—mainly the 2nd and 5th harmonics —commonly present during non-fault events. Figure 1a is the oscillography captured. Protective relays exploit this characteristic through harmonic restraint logic: Typical 2nd harmonic restraint thresholds range from 15% to 25% of the fundamental.